If I am running a #12 AWG conductor with a K value of 10.4 for a 120VAC single phase lighting circuit 200 ft, from the junction box inside the building. What voltage would be available at the load and would it meet the NEC recommendation?  If not, what would be the solution?     If I am running a 3-phase, 120V/208VAC feeder circuit from the first floor service panel to the second floor 200A lighting panel. The distance between is 120 ft.  If I use copper wire with a K value of 10.4, what size conductors should I use to meet the recommendations from the NEC for Voltage Drop?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.16MCQ
icon
Related questions
Question
  1. If I am running a #12 AWG conductor with a K value of 10.4 for a 120VAC single phase lighting circuit 200 ft, from the junction box inside the building. What voltage would be available at the load and would it meet the NEC recommendation?  If not, what would be the solution?

 

 

  1. If I am running a 3-phase, 120V/208VAC feeder circuit from the first floor service panel to the second floor 200A lighting panel. The distance between is 120 ft.  If I use copper wire with a K value of 10.4, what size conductors should I use to meet the recommendations from the NEC for Voltage Drop?
AI-Generated Solution
AI-generated content may present inaccurate or offensive content that does not represent bartleby’s views.
steps

Unlock instant AI solutions

Tap the button
to generate a solution

Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning