Example 3.5 Three single-phase transformers are connected in A-A to provide power for a three-phase wye- connected 200 kVA load with a 0.80 lagging power factor and an 80 kVA single-phase light load with a 0.90 lagging power factor, as shown in Figure 3.43. TAC I, BO 0.90 PF FIGURE 3.43 For Example 3.5. Application of Distribution Transformers 133 Assume that the three single-phase transformers have equal percent impedance and equal ratios of percent reactance to percent resistance. The primary-side voltage of the bank is 7,620/13,200 V and the secondary-side voltage is 240 V. Assume that the single-phase transformer connected between phases b and c is rated at 100 kVA and the other two are rated at 75 kVA. Determine the following: The line current flowino in each seconda "A*

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.26P: A bank of three single-phase transformers, each rated 30MVA,38.1/3.81kV, are connected in Y- with a...
icon
Related questions
Question
100%
Example 3.5
Three single-phase transformers are connected in A-A to provide power for a three-phase wye-
connected 200 kVA load with a 0.80 lagging power factor and an 80 kVA single-phase light load
with a 0.90 lagging power factor, as shown in Figure 3.43.
TAC
I,
BO
2.
RO kVA
0.90 PF
Co
FIGURE 3.43 For Example 3.5.
Application of Distribution Transformers
133
Assume that the three single-phase transformers have equal percent impedance and equal ratios
of percent reactance to percent resistance. The primary-side voltage of the bank is 7,620/13,200 V
and the secondary-side voltage is 240 V. Assume that the single-phase transformer connected
between phases b and c is rated at 100 kVA and the other two are rated at 75 kVA. Determine
the following:
a. The line current flowing in each secondary-phase wire
-"A*
Transcribed Image Text:Example 3.5 Three single-phase transformers are connected in A-A to provide power for a three-phase wye- connected 200 kVA load with a 0.80 lagging power factor and an 80 kVA single-phase light load with a 0.90 lagging power factor, as shown in Figure 3.43. TAC I, BO 2. RO kVA 0.90 PF Co FIGURE 3.43 For Example 3.5. Application of Distribution Transformers 133 Assume that the three single-phase transformers have equal percent impedance and equal ratios of percent reactance to percent resistance. The primary-side voltage of the bank is 7,620/13,200 V and the secondary-side voltage is 240 V. Assume that the single-phase transformer connected between phases b and c is rated at 100 kVA and the other two are rated at 75 kVA. Determine the following: a. The line current flowing in each secondary-phase wire -"A*
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 8 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning