A homeowner has asked to install a lighted mirror in a bathroom. The mirror contains eight 40-watt lamps. The bathroom circuit is connected to a single 120 Volts, 20 Ampere circuit breaker. At present, the circuit supplies power to an electric wall heater rated at 1000 Watts, a ceiling fan with a light kit, and a light fixture over the mirror. The fan motor has a full-load current draw of 3.2 Amperes and the light kit contains three 60 Watt lamps. The light fixture presently installed over the mirror contains four 60 Watt lamps.
We have been asked whether the present light fixture over the mirror can be replaced by the lighted mirror or not. It can be assumed that all loads are continuous, can the present circuit supply the power needed to operate all the loads without overloading the circuit.
Step by stepSolved in 6 steps with 2 images
- A moving coil instrument gives the full scale deflection of 10mA when the potential difference across it's terminals is 100 mV. Calculate (a) the shunt resistance for a full scale deflection corresponding to 100 A, and ( b) the series resistance for ful scale reading with 1000V. Calculate the power dissipation in each case.arrow_forwardwhat is the statement of Lenz law.arrow_forwardWhat is the unit E?arrow_forward
- 20.a. What's the primary disadvantage of using copper conductors?A. DurabilityB. CostC. AvailabilityD. Weight20.b. The NEC requires that each service-disconnecting means be suitable forA. hazardous locations.B. disconnecting the meter.C. wet conditions.D. the prevailing conditions 20.c. As a general rule, each building or structure is limited to a single service. What's an automatic exceptionto this rule?A. A second service deemed suitable for useB. A second service having the proper markingsC. Emergency systems or fire pumpsD. Higher building occupancyarrow_forward10. Identify the temperature range of Nickel wired RTD a. -100°_C to 300° C_ b. -80°_C to 200° C_ c. -80°_C to 600° C_ d. -80°_C to 300° C_arrow_forwardType MC Cable shall be secured at intervals not exceeding A. 3ft B. 4ft C. 6ft D. 8ftarrow_forward
- 3.a. There may be installations where grounded conductors of different systems are installed within the sameraceway, cable, or box. In these cases, it's imperative that the system-grounded conductors remainA. spliced.B. disconnected.C. separated.D. buried.3.b. In dwelling units, the maximum allowable voltage between conductors that supply lighting fixtures isA. 220 V.B. 120 V.C. 115 V.D. 110 V.arrow_forwardPlease answer in typing format solutionarrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,