b) Two synchronous generators, G2 and G2, are connected parallelly supplying a load. Generator G1 has a no-load frequency of 50.5 Hz and a slope of 300 MW/Hz. Generator G2 has a no-load frequency of 50.2 Hz and a slope of 500 MW/Hz. The load consumes 250 MW real power. (i) At what frequency does this system operate, and how much power is supplied by each of the two generators? (ii) An additional 100 MW load is added to this power system. What is the new system frequency, and how much power do G1 and G2 supply? (iii) The governor set point of G2 is changed to control system frequency back to 50 Hz. Determine the G2 governor set point.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.3MCQ: The amplitude of the sinusoidal symmetrical ac component of the three-phase short-circuit current of...
icon
Related questions
Question
100%
b) Two synchronous generators, G2 and G2, are connected parallelly
supplying a load. Generator G1 has a no-load frequency of 50.5 Hz and a
slope of 300 MW/Hz. Generator G2 has a no-load frequency of 50.2 Hz and
a slope of 500 MW/Hz. The load consumes 250 MW real power.
(1) At what frequency does this system operate, and how much power is
supplied by each of the two generators?
(ii) An additional 100 MW load is added to this power system. What is
the new system frequency, and how much power do G1 and G2
supply?
(iii) The governor set point of G2 is changed to control system frequency
back to 50 Hz. Determine the G2 governor set point.
Transcribed Image Text:b) Two synchronous generators, G2 and G2, are connected parallelly supplying a load. Generator G1 has a no-load frequency of 50.5 Hz and a slope of 300 MW/Hz. Generator G2 has a no-load frequency of 50.2 Hz and a slope of 500 MW/Hz. The load consumes 250 MW real power. (1) At what frequency does this system operate, and how much power is supplied by each of the two generators? (ii) An additional 100 MW load is added to this power system. What is the new system frequency, and how much power do G1 and G2 supply? (iii) The governor set point of G2 is changed to control system frequency back to 50 Hz. Determine the G2 governor set point.
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning