A generator having a solidly grounded neutral and rated 50 MVA, 30 kV has a positive, negative and zero sequence reactances of 20, 20 and 5 percent respectively. What reactance must be place in the generator neutral to limit the fault current or a bolted single line to ground fault to that for a bolted three phase fault?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.13P: Consider the oneline diagram of a simple power system shown in Figure 9.20. System data in per-unit...
icon
Related questions
icon
Concept explainers
Question
A generator having a solidly grounded neutral and rated 50
MVA, 30 kV has a positive, negative and zero sequence
reactances of 20, 20 and 5 percent respectively. What
reactance must be place in the generator neutral to limit
the fault current or a bolted single line to ground fault
to that for a bolted three phase fault?
Transcribed Image Text:A generator having a solidly grounded neutral and rated 50 MVA, 30 kV has a positive, negative and zero sequence reactances of 20, 20 and 5 percent respectively. What reactance must be place in the generator neutral to limit the fault current or a bolted single line to ground fault to that for a bolted three phase fault?
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning