A 50 Hz three-phase Y-connected 4 pole synchronous generator is rated at 15 kVA, 400 V (line-to-line). The synchronous reactance Xs per phase is 20. The no-load (open circuit, line-to line) teminal voltage follows the magnetisation curve shown in Figure Q2a below.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.4P
icon
Related questions
Question
A 50 Hz three-phase Y-connected 4 pole synchronous
generator is rated at 15 kVA, 400 V (line-to-line). The
synchronous reactance Xs per phase is 20. The no-load
(open circuit, line-to line) teminal voltage follows the
magnetisation curve shown in Figure Q2a below.
500
E 450
400
350
300
250
200
150
100
50
0.5
1
1.5
2.5
Field current (A)
Figure Q2a: Magnetisation curve for rotor of a synchronous
generator.
(i) Determine the rated speed.
(ii)
What is the field current required at full-load operation at
0.8 lagging pf.
(iii) Draw the phasor diagram for the mode of operation
described in (ii) above.
(iv) If the field current is set to 1.5 A, calculate the total
active power that is delivered by the machine when it is
operating as a generator connected to a 400 V (line-to-
line) infinite bus and making a torque angle of 5°.
Open-circuit terminal voltage (V)
Transcribed Image Text:A 50 Hz three-phase Y-connected 4 pole synchronous generator is rated at 15 kVA, 400 V (line-to-line). The synchronous reactance Xs per phase is 20. The no-load (open circuit, line-to line) teminal voltage follows the magnetisation curve shown in Figure Q2a below. 500 E 450 400 350 300 250 200 150 100 50 0.5 1 1.5 2.5 Field current (A) Figure Q2a: Magnetisation curve for rotor of a synchronous generator. (i) Determine the rated speed. (ii) What is the field current required at full-load operation at 0.8 lagging pf. (iii) Draw the phasor diagram for the mode of operation described in (ii) above. (iv) If the field current is set to 1.5 A, calculate the total active power that is delivered by the machine when it is operating as a generator connected to a 400 V (line-to- line) infinite bus and making a torque angle of 5°. Open-circuit terminal voltage (V)
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
HVDC
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning