A 400 V , 50 Hz ,three phase alternator ,rated at 200 kVA at a lagging power factor of 0.835 , is star connected and driven at 1500 rpm. The windings of the alternator have resistance 0.01 Ω and reactance, 0.118 Ω per phase at 50 Hz. The stator of the alternator has 96 slots, with 6 conductors per slot , in a double layer. To improve the wave form only 80 % of the pole pitch is wound. The alternator can be considered to have “constant overall efficiency” of 90 %. Determine the value of the maximum pole flux available to the alternator According to available information about the alternator described above it may be used to produce 60 Hz , provided the maximum phase current is limited to the same value as when operating at 50 Hz. Determine for the alternator ,when operated at 60 Hz: smallest power factor at which the current can deliver its rated load the rated output power

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question

A 400 V , 50 Hz ,three phase alternator ,rated at 200 kVA at a lagging power factor of 0.835 , is star connected and driven at 1500 rpm. The windings of the alternator have resistance 0.01 Ω and reactance, 0.118 Ω per phase at 50 Hz. The stator of the alternator has 96 slots, with 6 conductors per slot , in a double layer. To improve the wave form only 80 % of the pole pitch is wound. The alternator can be considered to have “constant overall efficiency” of 90 %.

Determine the value of the maximum pole flux available to the alternator

According to available information about the alternator described above it may be used to produce 60 Hz , provided the maximum phase current is limited to the same value as when operating at 50 Hz.

Determine for the alternator ,when operated at 60 Hz:

smallest power factor at which the current can deliver its rated load

the rated output power

Expert Solution
steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,