A 300MVA, 20KV three-phase generator has a reactance of 20%. The generator supplies a number of synchronous motors over a 64Km transmission line having transformers at both ends as shown on the one line diagram. The motors all rated 13.2KV are represented by two equivalent motors. Rated inputs to the motors are 200MVA and 100MVA for Ml and M2 respectively. For both motors X= 20%. The three-phase transformers T1 is rated 350MVA, 20/230KV with leakage reactance of 10%. Transformer T2 is composed of three single-phase transformers each rated 127/13.2KV, 100MVA with leakage reactance of 10%, series reactance of transmission line is 0.50/Km. Draw the reactance diagram with all reactance marked in per unit, select the generator rating as a base.
A 300MVA, 20KV three-phase generator has a reactance of 20%. The generator supplies a number of synchronous motors over a 64Km transmission line having transformers at both ends as shown on the one line diagram. The motors all rated 13.2KV are represented by two equivalent motors. Rated inputs to the motors are 200MVA and 100MVA for Ml and M2 respectively. For both motors X= 20%. The three-phase transformers T1 is rated 350MVA, 20/230KV with leakage reactance of 10%. Transformer T2 is composed of three single-phase transformers each rated 127/13.2KV, 100MVA with leakage reactance of 10%, series reactance of transmission line is 0.50/Km. Draw the reactance diagram with all reactance marked in per unit, select the generator rating as a base.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.49P
Related questions
Concept explainers
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
Question
![( A 300MVA, 20KV three-phase generator has a reactance of 20%. The
generator supplies a number of synchronous motors over a 64Km
transmission line having transformers at both ends as shown on the
one line diagram. The motors all rated 13.2KV are represented by two
equivalent motors. Rated inputs to the motors are 200MVA and
100MVA for M1 and M2 respectively. For both motors X= 20%. The
three-phase transformers T1 is rated 350MVA, 20/230KV with
leakage reactance of 10%. Transformer T2 is composed of three
single-phase transformers each rated 127/13.2KV, 100MVA with
leakage reactance of 10%, series reactance of transmission line is
0.52/Km. Draw the reactance diagram with all reactance marked in
per unit, select the generator rating as a base.
(M1
230KV
G1)
(M2
20KV](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F8a9ddf80-1af6-49da-ad7d-7947cb5c0910%2Fc2f250ca-37eb-4d36-a7a8-6ce40b30bad4%2Fdct5k5d_processed.jpeg&w=3840&q=75)
Transcribed Image Text:( A 300MVA, 20KV three-phase generator has a reactance of 20%. The
generator supplies a number of synchronous motors over a 64Km
transmission line having transformers at both ends as shown on the
one line diagram. The motors all rated 13.2KV are represented by two
equivalent motors. Rated inputs to the motors are 200MVA and
100MVA for M1 and M2 respectively. For both motors X= 20%. The
three-phase transformers T1 is rated 350MVA, 20/230KV with
leakage reactance of 10%. Transformer T2 is composed of three
single-phase transformers each rated 127/13.2KV, 100MVA with
leakage reactance of 10%, series reactance of transmission line is
0.52/Km. Draw the reactance diagram with all reactance marked in
per unit, select the generator rating as a base.
(M1
230KV
G1)
(M2
20KV
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 6 steps with 2 images
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning