6. Two alternators running in parallel supply a lighting load of 2000KW and a motor load of 4000KW at p.f. 0.8 lagging. One machine is loaded to 2400KW at p.f. 0.95 lagging. What is the output and power factor of the second machine? (Ans. 3600 KW, 2211.16 KVAR, 0.8521 lag.)
6. Two alternators running in parallel supply a lighting load of 2000KW and a motor load of 4000KW at p.f. 0.8 lagging. One machine is loaded to 2400KW at p.f. 0.95 lagging. What is the output and power factor of the second machine? (Ans. 3600 KW, 2211.16 KVAR, 0.8521 lag.)
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.16P: A single-phase, 120V(rms),60Hz source supplies power to a series R-L circuit consisting of R=10 and...
Related questions
Question
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 3 steps with 2 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning