2,500 kVA, three-phase, 60-Hz, 6.6 kV delta-connected alternator has a field resistance of 0.45 Ω and an armature resistance of 0.05 Ω per phase. The field current at full load 0.85 power factor is 200 A. The stray power losses amount to 82 kW. Calculate the efficiency of the alternator.
Synchronous Generator
In comparison to an asynchronous generator, it is a machine where the rotor speed is equal to the rotating magnetic field produced by the stator, i.e., mechanical speed is equal to the electrical speed, thus called synchronous, and not asynchronous.
Salient Pole Rotor
Salient pole rotor includes a large number of exposed poles mounted on a magnetic wheel. The construction of a bright pole is as shown in the image on the left. The proposed poles are made of metal laminations. The rotor winding is provided on these poles and is supported by pole shoes.
A 2,500 kVA, three-phase, 60-Hz, 6.6 kV delta-connected alternator has a field resistance of 0.45 Ω and an armature resistance of 0.05 Ω per phase. The field current at full load 0.85 power factor is 200 A. The stray power losses amount to 82 kW. Calculate the efficiency of the alternator.
Step by step
Solved in 2 steps with 1 images