Homework5Sol
pdf
School
University of British Columbia *
*We aren’t endorsed by this school
Course
453
Subject
Electrical Engineering
Date
Dec 6, 2023
Type
Pages
7
Uploaded by MateRose22143
ELEC 453 – Power System Analysis
Fall 2023
Homework 5 Solution
Due Date:
Thursday, November 9, 2023
Reading:
Chapters 3.1–3.5 in 7th edition textbook
Problem 1.
The following data are obtained when open-circuit and short-circuit tests are performed on
a single-phase, 50-kVA, 2400/240-volt, 60-Hz distribution transformer
Measurement on low-voltage side with high-voltage winding open.
Voltage: 240 V. Current: 5.97 A. Power: 213 W.
Measurements on high-voltage side with low-voltage winding shorted.
Voltage: 60 V. Current: 20.8 A. Power: 750 W.
1. Neglecting the series impedance, determine the exciting admittance referred to the high-voltage side.
The open circuit test data can be used to find the exciting admittance by neglecting the series
impedance. First, we compute the turns ratio as
a
=
V
1
,rated
V
2
,rated
=
2400
240
= 10
.
G
c
,
Y
m
, and
B
m
are then determined as follows:
G
c
=
P
2
V
2
1
=
213
2400
2
= 3
.
698
×
10
−
5
S
,
|
Y
m
|
=
I
1
V
1
=
1
a
I
2
V
1
=
0
.
1
·
5
.
97
2400
= 2
.
488
×
10
−
4
S
,
B
m
=
p
|
Y
m
|
2
−
G
2
c
=
p
(2
.
488
×
10
−
4
)
2
−
(3
.
698
×
10
−
5
)
2
= 2
.
460
×
10
−
4
S
,
Y
m
=
G
c
−
jB
m
= 3
.
698
×
10
−
5
−
j
2
.
460
×
10
−
4
= 2
.
488
×
10
−
4
∠
−
81
.
45
◦
S
.
1
2. Neglecting the exciting admittance, determine the equivalent series impedance referred to the high-
voltage side.
The short circuit test data can be used to find the equivalent series impedance referred to the high-
voltage side. The rated current for the high-voltage side is
I
1
,rated
=
S
rated
V
1
,rated
=
50000
2400
= 20
.
83 A
.
R
eq
1
,
Z
eq
1
, and
X
eq
1
are then determined as follows:
R
eq
1
=
P
1
I
2
1
,rated
=
750
20
.
83
2
= 1
.
728 Ω
|
Z
eq
1
|
=
V
1
I
1
,rated
=
60
20
.
83
= 2
.
880 Ω
X
eq
1
=
q
|
Z
eq
1
|
2
−
R
2
eq
1
=
p
2
.
880
2
−
1
.
728
2
= 2
.
305 Ω
Z
eq
1
=
R
eq
1
+
jX
eq
1
= 1
.
728 +
j
2
.
305 = 2
.
880
∠
53
.
14
◦
Ω
3. Assuming equal series impedances for the primary and referred secondary, obtain an equivalent T-
circuit referred to the high-voltage side.
Problem 2.
A single-phase 50-kVA, 2400/240-volt, 60-Hz distribution transformer is used as a step-down
transformer at the load end of a 2400-volt feeder whose series impedance is (1.0 + j2.0) Ω. The equivalent
series impedance of the transformer is (1.0 + j2.5) Ω referred to the high-voltage (primary) side.
The
transformer is delivering rated load at 0.8 power factor lagging and at rated secondary voltage. Neglecting
the transformer exciting current, determine:
1. The voltage at the transformer primary terminals.
A circuit representation of the feeder and transformer is as follows:
The voltage at the transformer primary terminals is denoted by
¯
V
1
. Let
¯
V
2
denote the voltage at the
secondary terminals and set
¯
V
2
with reference angle 0. Then, the secondary-side current is
¯
I
2
=
¯
S
rated
¯
V
2
∗
=
50000
∠
cos
−
1
0
.
8
240
∠
0
◦
∗
= 208
.
3
∠
−
36
.
87
◦
A
.
The current referred to the primary side is
¯
I
1
=
¯
I
2
a
=
208
.
3
∠
−
36
.
87
◦
10
= 20
.
83
∠
−
36
.
87
◦
A
.
The voltage at the primary side of the ideal transformer is
¯
E
1
=
a
¯
V
2
= 10
·
240
∠
0
◦
= 2400
∠
0
◦
V.
Then, we get
¯
V
1
=
¯
E
1
+
¯
Z
eq
¯
I
1
= 2400
∠
0
◦
+ (1
.
0 +
j
2
.
5)(20
.
83
∠
−
36
.
87
◦
) = 2448
∠
0
.
683
◦
V
.
2. The voltage at the sending end of the feeder.
¯
V
s
=
¯
V
1
+
¯
Z
feed
¯
I
1
= 2448
∠
0
.
683
◦
+ (1
.
0 +
j
2
.
0)(20
.
83
∠
−
36
.
87
◦
) = 2490
∠
1
.
150
◦
V
3. The real and reactive power delivered to the sending end of the feeder. The complex power at the
sending end of the feeder is
¯
S
s
=
¯
V
s
¯
I
∗
1
= (2490
∠
1
.
150
◦
)(20
.
83
∠
−
36
.
87
◦
)
∗
= 40
.
861 +
j
31
.
948 kVA
.
Therefore, the real and reactive power delivered at the sending end are
P
s
= 40
.
861 kW
,
Q
s
= 31
.
948 kVar
.
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Problem 3.
A three-phase generator rated 300 MVA, 23 kV, is supplying a system load of 240 MVA and
0.9 power factor lagging at 230 kV through a 330 MVA, 23 kV Delta-230 kV Wye step-up transformer
with a leakage reactance of 0.11 p.u. Use
¯
V
A
= 1
.
0
∠
0
◦
as reference.
1. Neglecting the exciting current and choosing base values at the load of 100 MVA and 230 kV, find
the phasor currents
I
A
,
I
B
, and
I
C
supplied to the load in per unit (magnitude and angle).
The current drawn by each phase of the load is
¯
I
A
=
¯
S
load
1
ϕ
¯
V
A
=
(240
/
3)
×
10
6
∠
cos
−
1
0
.
9
(230
/
√
3)
×
10
3
∠
0
◦
∗
= 602
.
45
∠
−
25
.
84
◦
A
,
¯
I
B
=
¯
S
load
1
ϕ
¯
V
B
=
(240
/
3)
×
10
6
∠
cos
−
1
0
.
9
(230
/
√
3)
×
10
3
∠
−
120
◦
∗
= 602
.
45
∠
−
145
.
84
◦
A
,
¯
I
C
=
¯
S
load
1
ϕ
¯
V
C
=
(240
/
3)
×
10
6
∠
cos
−
1
0
.
9
(230
/
√
3)
×
10
3
∠
120
◦
∗
= 602
.
45
∠
94
.
16
◦
A
,
The base quantities are
S
base,
3
ϕ
= 100 MVA
,
V
base,ll
= 230 kV
,
I
base
=
S
base
1
ϕ
V
base,ln
=
100
/
3
×
10
6
230
/
√
3
×
10
3
= 251
.
02 A
.
Therefore, the current drawn by each phase of the load, in per-unit, is
¯
I
A,pu
=
¯
I
A
I
base
=
602
.
45
∠
−
25
.
84
◦
251
.
02
= 2
.
4
∠
−
25
.
84
◦
p.u.
,
¯
I
B,pu
=
¯
I
B
I
base
=
602
.
45
∠
−
145
.
84
◦
251
.
02
= 2
.
4
∠
−
145
.
84
◦
p.u.
,
¯
I
C,pu
=
¯
I
C
I
base
=
602
.
45
∠
94
.
16
◦
251
.
02
= 2
.
4
∠
94
.
16
◦
p.u.
.
2. Draw the per phase equivalent circuit and compute the phasor currents
I
a
,
I
b
, and
I
c
, from the
generator in per unit. (Note: Take into account the phase shift of the transformer.)
The high-voltage side leads low-voltage side by 30
◦
. So on the low-voltage side, in per-unit,
¯
I
a,pu
= 2
.
4
∠
−
55
.
84
◦
p.u.
,
¯
I
b,pu
= 2
.
4
∠
−
175
.
84
◦
p.u.
,
¯
I
c,pu
= 2
.
4
∠
64
.
16
◦
p.u.
.
3. Find the generator terminal voltage magnitude in kV and the total three-phase real power supplied
by generator in MW.
Even though the leakage reactance
X
l
is given in per unit, this is per unit with respect to the
low-voltage side transformer. So we convert this to per-unit value in the system base.
X
l,p.u.
=
X
l
Z
base,sys
Z
base,low
=
X
l
V
2
base,low
S
base,low
V
2
base,sys
S
base,sys
= 0
.
11
23
2
330
23
2
100
!
= 0
.
11
100
330
= 0
.
0333 p.u.
The high-voltage side leads low-voltage side by 30
◦
. So on the low-voltage side,
¯
V
a,pu
= 1
∠
−
30
◦
p.u.
.
Therefore,
¯
V
G,pu
=
¯
I
a,pu
(
jX
l,pu
) +
¯
V
a,pu
= (2
.
4
∠
−
55
.
84
◦
)(
j
0
.
033) + 1
∠
−
30
◦
= 1
.
037
∠
−
26
.
02
◦
p.u.
Then,
|
¯
V
G
|
=
V
base,low
|
¯
V
G,pu
|
= 23(1
.
037) = 23
.
86 kV
.
The complex power supplied by the generator is
¯
S
G,pu
=
¯
V
G,pu
¯
I
∗
a,pu
= (1
.
037
∠
−
26
.
02
◦
)(2
.
4
∠
−
55
.
84
◦
)
∗
= 2
.
16 +
j
1
.
24 p.u.
,
which corresponds to 2.16 p.u. or 216 MW real power supplied. This matches the real power absorbed
(240
×
0
.
9 = 216 MW) since there are no
I
2
R
losses.
4. By omitting the transformer phase shift altogether, check to see whether you get the same magnitude
of generator terminal voltage and real power delivered by the generator (must show work).
By omitting the transformer phase shift, the high-voltage side and low-voltage side have the same
phase shift. So on the low-voltage side,
¯
V
a,pu
= 1
∠
0
◦
p.u.
.
Therefore,
¯
V
G,pu
=
¯
I
a,pu
(
jX
l,pu
) +
¯
V
a,pu
= (2
.
4
∠
−
25
.
84
◦
)(
j
0
.
033) + 1
∠
0
◦
= 1
.
037
∠
3
.
98
◦
p.u.
Then,
|
¯
V
G
|
=
V
base,low
|
¯
V
G,pu
|
= 23(1
.
037) = 23
.
86 kV
.
¯
S
G,pu
=
¯
V
G,pu
¯
I
∗
a,pu
= (1
.
037
∠
3
.
98
◦
)(2
.
4
∠
−
25
.
84
◦
)
∗
= 2
.
16 +
j
1
.
24 p.u.
Problem 4.
Consider the system below. Select a base of 100 MVA and 161 kV in Zone 2.
The 3
ϕ
line-to-neutral rated values are given:
G
: 150 MVA, 14.2 kV,
X
′
d
= 0
.
3 Ω
T
1
: 250 MVA, 13.8 - 161 kV,
X
T
1
= 0
.
15 Ω referred to the low-voltage side
T
2
: 150 MVA, 161 - 13.2 kV,
X
T
2
= 0
.
2 Ω referred to the low-voltage side
Line: ¯
z
line
=
j
100 Ω
1. Fill in the table below.
Zone 1
Zone 2
Zone 3
Base Voltage
13
.
8 kV
161 kV
13
.
2 kV
Base Power
100 MVA
100 MVA
100 MVA
Base Impedance
(
13
.
8
×
10
3
)
2
100
×
10
6
= 1
.
9044 Ω
(
161
×
10
3
)
2
100
×
10
6
= 259
.
21 Ω
(
13
.
2
×
10
3
)
2
100
×
10
6
= 1
.
7424 Ω
2. Fill in per-unit values for:
1)
V
G
=
14
.
2
13
.
8
= 1
.
029 p.u.
2)
X
′
d
=
0
.
3
1
.
9044
= 0
.
1575 p.u.
3)
X
T
1
=
0
.
15
1
.
9044
= 0
.
0788 p.u.
4) ¯
z
line
=
j
100
259
.
21
=
j
0
.
3858 p.u.
5)
X
T
2
=
0
.
2
1
.
7424
= 0
.
1148 p.u.
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
3. Draw the per-phase diagram using per-unit quantities. Label figure with quantities from (2).
φ
+
-
φ
4. The generator is delivering 90 MW at 0.9 p.f.
lagging with terminal voltage 14.2 kV. In per-unit
quantities, compute generator current
¯
I
G
.
¯
S
Gϕ
= 0
.
3 +
j
0
.
3
×
tan
(
cos
−
1
0
.
9
)
= 0
.
3 +
j
0
.
145
p.u.
¯
I
Gϕ
=
¯
S
Gϕ
¯
V
Gϕ
∗
=
0
.
3 +
j
0
.
145
1
.
029
∠
0
◦
∗
= 0
.
3238
∠
−
25
.
8
◦
p.u.
5. In actual quantities, determine the line-to-neutral voltage at the load terminal.
¯
V
LNϕ
=
¯
V
Gϕ
−
j
¯
I
Gϕ
(
X
T
1
+
X
line
+
X
T
2
)
V
base
= [1
.
029
∠
0
◦
−
j
(0
.
3238
∠
−
25
.
8
◦
) (0
.
0788 + 0
.
3858 + 0
.
1148)]
×
13
.
2
= (0
.
9623
∠
−
10
.
11
◦
)
×
13
.
2 = 12
.
70
∠
−
10
.
11
◦
kV
6. In per-unit quantities and using the ZIP model, describe a possible load that fits this circuit.
All types of loads are possible:
constant power load
constant impedance load
constant current load
Related Documents
Related Questions
CALCULATE REACTANCE( NEED ONLY HANDWRITTEN SOLUTION PLEASE OTHERWISE DOWNVOTE).
arrow_forward
A 100 KVA, 2000/200V 1-phase 2-winding Transformer is to be used as an auto
transformer for stepping up the voltage from 2000 V to 2200 V. At rated load, the
2-winding Transformer has 2.5% loss, 3% voltage regulation & 4% impedance for an auto
transformer determine
(a) Voltage & current rating
(b) KVA rating
(c) Effiiency
(d) Percentage impedance
(c) Voltage regulation
(f) Short circuit current on each side.
arrow_forward
Please answer it properly because it's second time, I already ask this question before but the answer was only blank sheet of paper... I'm paying rightfully so give me an answer also right and correctly!!!
Thank you.
arrow_forward
2. What type of potential transformer would you use for a 362-kV grounded-neutral metering application
on an interconnection system?
A. Bar-type
B. Cascade-type
C. Window-type
D. Phase-shift-type
arrow_forward
3.14 A single-phase 50-kVA, 2400/240-volt, 60-Hz distribution transformer is
used as a step-down transformer at the load end of a 2400-volt feeder
whose series impedance is (1.0 + j2.0) ohms. The equivalent series
impedance of the transformer is (1.0 + j2.5) ohms referred to the high-
voltage (primary) side. The transformer is delivering rated load at a 0.8
power factor lagging and at a rated secondary voltage. Neglecting the
transformer exciting current, determine (a) the voltage at the transformer
primary terminals, (b) the voltage at the sending end of the feeder, and
(c) the real and reactive power delivered to the sending end of the feeder.
arrow_forward
Electrical Machine transformer question. please show steps.
arrow_forward
8. A three-phase 50 Hz, 200 MVA, 220/66 kV transformer has a clock number of Yd11. The
transformer winding resistances are 2.0 N and 0.12 A, and the leakage reactances are 10 0
and 0.6 N for the high voltage side and low voltage side respectively.
(a) Sketch the phase voltage phasor diagrams for the high-voltage side and low-voltage side of
the transformer and from the phasor diagrams obtain its connection diagram.
(b) Calculate the per-unit impedance of the transformer referred to the high-voltage side.
(c) Calculate the full-load copper losses of this transformer.
(d) Calculate the efficiency of the transformer when it supplies 90% of full-load at a power
factor of 0.85 lagging, if the core losses are equal to 3 MW.
arrow_forward
Problem 2. A 150-MVA, 220/22-kV, three-phase has the following parameters (in 2):
R, = 0.1
R2 = 0.001
Xm= 7800
X, = 0.25
X, = 0.002
R = 30250
%3D
The transformer is operating in step-down mode and delivering hafl of rated load at 22.5kV and 0.86 power
factor lagging.
a) Determine the equivalent circuit referred to the high-voltage side;
b) Find the primary voltage and current;
c) Determine the voltage regulation.
d) Determine the efficiency.
arrow_forward
QUESTION TWOo
A three-phase 50 Hz, 200 MVA, 220/66 kV transformer has a clock number of Yd11. The
transformer winding resistances are 2.0 N and 0.12 N, and the leakage reactances are 10 N and
0.6 N for the high voltage side and low voltage side respectively.
(a) Sketch the phase voltage phasor diagrams for the high-voltage side and low-voltage side of
the transformer and from the phasor diagrams obtain its connection diagram.
(b) Calculate the per-unit impedance of the transformer referred to the high-voltage side.
(c) Calculate the full-load copper losses of this transformer.
(d) Calculate the efficiency of the transformer when it supplies 90% of full-load at a power factor
of 0.85 lagging, if the core losses are equal to 1.6 MW.
(e) Suggest the most suitable method of cooling this transformer and explain how the suggested
method works.
() Why are most power transformers and distribution transformers' tanks oil-filled?
To increase the supply capacity, the transformer described above…
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you

Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Related Questions
- CALCULATE REACTANCE( NEED ONLY HANDWRITTEN SOLUTION PLEASE OTHERWISE DOWNVOTE).arrow_forwardA 100 KVA, 2000/200V 1-phase 2-winding Transformer is to be used as an auto transformer for stepping up the voltage from 2000 V to 2200 V. At rated load, the 2-winding Transformer has 2.5% loss, 3% voltage regulation & 4% impedance for an auto transformer determine (a) Voltage & current rating (b) KVA rating (c) Effiiency (d) Percentage impedance (c) Voltage regulation (f) Short circuit current on each side.arrow_forwardPlease answer it properly because it's second time, I already ask this question before but the answer was only blank sheet of paper... I'm paying rightfully so give me an answer also right and correctly!!! Thank you.arrow_forward
- 2. What type of potential transformer would you use for a 362-kV grounded-neutral metering application on an interconnection system? A. Bar-type B. Cascade-type C. Window-type D. Phase-shift-typearrow_forward3.14 A single-phase 50-kVA, 2400/240-volt, 60-Hz distribution transformer is used as a step-down transformer at the load end of a 2400-volt feeder whose series impedance is (1.0 + j2.0) ohms. The equivalent series impedance of the transformer is (1.0 + j2.5) ohms referred to the high- voltage (primary) side. The transformer is delivering rated load at a 0.8 power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.arrow_forwardElectrical Machine transformer question. please show steps.arrow_forward
- 8. A three-phase 50 Hz, 200 MVA, 220/66 kV transformer has a clock number of Yd11. The transformer winding resistances are 2.0 N and 0.12 A, and the leakage reactances are 10 0 and 0.6 N for the high voltage side and low voltage side respectively. (a) Sketch the phase voltage phasor diagrams for the high-voltage side and low-voltage side of the transformer and from the phasor diagrams obtain its connection diagram. (b) Calculate the per-unit impedance of the transformer referred to the high-voltage side. (c) Calculate the full-load copper losses of this transformer. (d) Calculate the efficiency of the transformer when it supplies 90% of full-load at a power factor of 0.85 lagging, if the core losses are equal to 3 MW.arrow_forwardProblem 2. A 150-MVA, 220/22-kV, three-phase has the following parameters (in 2): R, = 0.1 R2 = 0.001 Xm= 7800 X, = 0.25 X, = 0.002 R = 30250 %3D The transformer is operating in step-down mode and delivering hafl of rated load at 22.5kV and 0.86 power factor lagging. a) Determine the equivalent circuit referred to the high-voltage side; b) Find the primary voltage and current; c) Determine the voltage regulation. d) Determine the efficiency.arrow_forwardQUESTION TWOo A three-phase 50 Hz, 200 MVA, 220/66 kV transformer has a clock number of Yd11. The transformer winding resistances are 2.0 N and 0.12 N, and the leakage reactances are 10 N and 0.6 N for the high voltage side and low voltage side respectively. (a) Sketch the phase voltage phasor diagrams for the high-voltage side and low-voltage side of the transformer and from the phasor diagrams obtain its connection diagram. (b) Calculate the per-unit impedance of the transformer referred to the high-voltage side. (c) Calculate the full-load copper losses of this transformer. (d) Calculate the efficiency of the transformer when it supplies 90% of full-load at a power factor of 0.85 lagging, if the core losses are equal to 1.6 MW. (e) Suggest the most suitable method of cooling this transformer and explain how the suggested method works. () Why are most power transformers and distribution transformers' tanks oil-filled? To increase the supply capacity, the transformer described above…arrow_forward
arrow_back_ios
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning

Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning