What is the wet bulb temperature of the indoor air that is being recirculated

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter22: Condensers
Section: Chapter Questions
Problem 6RQ: A water-cooling tower capacity is governed by what aspect of the ambient air? A. Dry-bulb...
icon
Related questions
Question

Recirculated air from the indoor space is 7,500 cfm (75 degrees F dry bulb, 50% RH). Ventilation air from outdoors is 2,500 cfm (95 degrees F dry bulb, 76 degrees F wet bulb). Leaving air off the cooling coil is 10,000 cfm (55 degrees F dry bulb, 90% RH). What is the wet bulb temperature of the indoor air that is being recirculated?

Group of answer choices

61.5 degrees

63.5 degrees

62.5 degrees

61 degrees