Question

Avapour compression refrigeration system using refrigerant F-12 is employed to produce 8640 kg of ice per day. The condensing and evaporating temperature of refrigerant are 48°C and -20°C respectively. Saturated liquid leaves the condenser and saturated vapour leaves the evaporator. Compression is isentropic, water at 35 C is used to form the ice. The temperature of ice should be-8°C. Heat flow into the orme tank from surroundings may be taken as 10% of total heat absorbed from

water to form ice. Determine the power required to drive the compressor. Take specific heat of ice = 2,26 kJ/kg-K. Latent heat of Ice= 335 kJ/kg. Specific heat of water =

4.2 kJ/kg-K. 

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning