Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C 42°C Condenser Expansion valve Water 18°C Evaporator -M Sim QL 2 1.2 MPa 65°C lin Win Compressor 60 kPa -34°C Determine the COP of the refrigerator. (You must provide an answer before moving on to the next part.) The COP of the refrigerator is

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter3: Refrigeration And Refrigerants
Section: Chapter Questions
Problem 2RQ: What are the approximate temperature ranges tor low-, medium-, and high-temperature refrigeration...
icon
Related questions
Question
Required information
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by
rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C.
The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60
kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat
exchanger loses no heat to the environment.
26°C
42°C
↓
Condenser
3
Expansion
valve
Water
18°C
Evaporator
QL
(2)
1.2 MPa
65°C
lin
Win
Compressor
60 kPa
-34°C
Determine the COP of the refrigerator. (You must provide an answer before moving on to the next part.)
The COP of the refrigerator is
< Prev
89
of 9
Next >
Transcribed Image Text:Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C 42°C ↓ Condenser 3 Expansion valve Water 18°C Evaporator QL (2) 1.2 MPa 65°C lin Win Compressor 60 kPa -34°C Determine the COP of the refrigerator. (You must provide an answer before moving on to the next part.) The COP of the refrigerator is < Prev 89 of 9 Next >
Expert Solution
steps

Step by step

Solved in 3 steps with 5 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning