In the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generators are connected in star with thier star points grounded. The system base is 15 MVA. The transformers all have reactances of 0.04 p.u. on this 15 MVA base. The reactances of all other elements are given in Table 1 (in $2) and the voltage levels are given in Table 2. 2 T1 L 01/10 jä 3 T3 p.u. Per-Unit Convert all values to p.u. on a 15 MVA base. Xax= Xc₂= XL = p.u. p.u. G1 V BABE Figure 1: A section of the distribution system X G1 T1 G1 9/10 4 Table 1: Sequence reactances (12) 0.3 0.59 0.01 L G2 Fault Voltage What is the voltage at bus 3 (in Volts) after the fault has occurred? V T2 10 10/4 Table 2: Voltage bases (kV) T2 G2 T3 5 10/9 G2 Fault Current A three-phase fault with a fault reactance of 0.01 p.u. occurs at bus 3. Calculate the fault current flowing at the fault point in kA. IF=j KA Sc Unan

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.26P: A bank of three single-phase transformers, each rated 30MVA,38.1/3.81kV, are connected in Y- with a...
icon
Related questions
Question
In the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generators are connected in
star with thier star points grounded. The system base is 15 MVA. The transformers all have reactances of 0.04 p.u. on this 15 MVA base. The
reactances of all other elements are given in Table 1 (in 2) and the voltage levels are given in Table 2.
p.u.
G1
p.u.
T1
jö
Per-Unit
Convert all values to p.u. on a 15 MVA base.
Xa=
p.u.
Xc₂=
XL =
V BABE
G1
2
X
9
T3
Figure 1: A section of the distribution system
T1
L
Table 1: Sequence reactances (2)
3
G1 L G2
0.3 0.59 0.01
4
L
9/10 10
Fault Voltage
What is the voltage at bus 3 (in Volts) after the fault has occurred?
Vp=
V
T2
5
T2
34
10/4
Table 2: Voltage bases (kV)
G2
4
T3
10/9
|
G2
Fault Current
A three-phase fault with a fault reactance of 0.01 p.u. occurs at bus 3. Calculate the fault current flowing at the fault point in KA.
Ip=-j
KA
So
Transcribed Image Text:In the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generators are connected in star with thier star points grounded. The system base is 15 MVA. The transformers all have reactances of 0.04 p.u. on this 15 MVA base. The reactances of all other elements are given in Table 1 (in 2) and the voltage levels are given in Table 2. p.u. G1 p.u. T1 jö Per-Unit Convert all values to p.u. on a 15 MVA base. Xa= p.u. Xc₂= XL = V BABE G1 2 X 9 T3 Figure 1: A section of the distribution system T1 L Table 1: Sequence reactances (2) 3 G1 L G2 0.3 0.59 0.01 4 L 9/10 10 Fault Voltage What is the voltage at bus 3 (in Volts) after the fault has occurred? Vp= V T2 5 T2 34 10/4 Table 2: Voltage bases (kV) G2 4 T3 10/9 | G2 Fault Current A three-phase fault with a fault reactance of 0.01 p.u. occurs at bus 3. Calculate the fault current flowing at the fault point in KA. Ip=-j KA So
Expert Solution
steps

Step by step

Solved in 6 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L