A three-phase motor takes 10 kVA at 0.6 lagging from a source of 230 volts. It is in parallel with a balanced delta load having 16 ohms resistance and 12 ohms capacitive reactance in series in each phase. Determine the total line current. 31.24 A 32.04 A 34.55 A 30.05 A

Electricity for Refrigeration, Heating, and Air Conditioning (MindTap Course List)
10th Edition
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Russell E. Smith
Chapter9: Components For Electric Motors
Section: Chapter Questions
Problem 9RQ
icon
Related questions
Question
A three-phase motor takes 10 kVA at 0.6 lagging from a source of 230 volts. It is in
parallel with a balanced delta load having 16 ohms resistance and 12 ohms capacitive
reactance in series in each phase. Determine the total line current.
31.24 A
32.04 A
34.55 A
30.05 A
Transcribed Image Text:A three-phase motor takes 10 kVA at 0.6 lagging from a source of 230 volts. It is in parallel with a balanced delta load having 16 ohms resistance and 12 ohms capacitive reactance in series in each phase. Determine the total line current. 31.24 A 32.04 A 34.55 A 30.05 A
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three phase Induction Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning